ERR02 – Over-Current During Acceleration
What this means
ERR02 occurs when the VFD detects too much current while the spindle is accelerating up to speed. This happens before the spindle reaches its commanded RPM, typically right at startup or just as cutting begins.
In simple terms, the spindle is being asked to spin up faster or under more load than the electrical system can safely support.
Most Common Causes (Real-World)
1. Acceleration time is too aggressive
This is the most common cause of ERR02.
If the spindle is commanded to reach full RPM too quickly, the inrush current during acceleration can exceed safe limits.
What we typically ship:
-
Acceleration time set to 6 seconds
Depending on tooling, material, and electrical conditions, some setups benefit from slowing this down.
2. Controller and VFD acceleration times do not match
This is especially important for controllers like Masso.
If:
-
You increase acceleration time in the VFD, but
-
Do not update the spindle acceleration time in the controller
the machine may begin moving into the material before the spindle is fully up to speed, causing a sudden load spike that trips ERR02.
Both values must match.
3. Sudden load during startup
Examples:
-
Straight plunges into material
-
No ramp or lead-in
-
Tool already engaged when the spindle starts
Any abrupt load during acceleration can cause current to spike.
4. Low or unstable input voltage
During acceleration, the spindle draws more power. If the input voltage dips:
-
The VFD compensates by pulling more current
-
This can trigger an over-current fault
This can happen even on dedicated circuits due to:
-
Long wiring runs
-
Loose outlets or terminals
-
Other large motors starting on the same electrical service
5. Motor cable or grounding issues
Less common, but worth checking:
-
Loose motor connections
-
Excessively long motor cables
-
Ground faults or damaged insulation
What to Do First (Recommended Order)
Step 1: Increase acceleration time
This resolves the vast majority of ERR02 cases.
-
Increase the VFD acceleration time
Parameter: P0.0.11 -
Try increasing from 6 seconds to 8 seconds or higher
⚠️ Important for Masso users:
Also update the Spindle Acceleration Time in Masso’s spindle setup to match the VFD value exactly.
Step 2: Reduce startup load
-
Use ramped tool entries instead of straight plunges
-
Avoid starting the spindle while already engaged in material
-
Reduce plunge rate if needed
Step 3: Check electrical supply
-
Plug the VFD directly into the wall outlet
-
Avoid extension cords or power strips
-
Verify input terminals at the VFD are tight
Step 4: Inspect motor wiring
-
Confirm motor cable connections are secure
-
Check for damage or pinched cables
-
Verify proper grounding
Important Notes
-
ERR02 is a protective fault, not a failure
-
It does not indicate a damaged spindle
-
Repeated ERR02 events are a sign the acceleration profile or startup load needs adjustment
Summary
ERR02 means the spindle is being overloaded while accelerating.
In almost all cases:
-
Increase acceleration time
-
Ensure controller and VFD acceleration settings match
-
Avoid sudden load at startup
If ERR02 persists after increasing acceleration time and reducing startup load, contact support with details about your controller, spindle RPM, tool type, and cutting strategy.